Real Estate Standards
Any planning permit for the construction or major renovation of an office building submitted after January 1, 2015 must comply with the passive standard. An exemption regime is also provided when the building configuration is unfavorable.
For OFFICES, new construction or demolition/reconstruction
The EPB requirements to be met will be as follows:
- A net heating requirement less than or equal to 15 kWh per m² per year (five times less than the consumption of a standard office building)
- A net cooling requirement less than or equal to 15 kWh per m² per year (five times less than the consumption of a standard office building)
- Primary energy consumption for heating, cooling, lighting and electrical auxiliaries less than or equal to (95 – 2.5 *min (C; 4)) kWh per m² per year, where C is defined as compactness, i.e. the ratio between the protected volume and the heat loss area (five times less than the consumption of a standard office building)
- An overheating temperature that may not exceed 25°C for more than 5% of the usage period
For all planning permits submitted from January 1, 2018, an additional requirement is planned: air tightness under 50 Pa less than or equal to 0.6 volume per hour.
When the configuration of the tertiary building is unfavorable, namely low solar gains (shading, poor orientation) and/or poor compactness, an automatic exemption regime is implemented. The requirements to be met will be:
A net heating requirement less than or equal to X kWh per m² per year, where the net heating requirement X is calculated with:
- A weighted average of 0.12 W/m²K for opaque walls
- A weighted average of 0.85 W/m²K for all windows and doors
- Air tightness under 50 Pa equal to:
| 2015 | 2016 | 2017 | 2018 |
| 1 vol per hour | 0.8 vol per hour | 0.7 vol per hour | 0.6 vol per hour |
- A ventilation system with a default recovery efficiency of 75% and a default good installation setting (mheat,sec i = 1)
- Any other parameter to be encoded is realistic for the case studied
Primary energy consumption for heating, cooling, lighting and electrical auxiliaries less than or equal to (95 – 2.5 *min (C; 4)) + 1.2*(X – 15) kWh per m² per year, where C is defined as compactness, i.e. the ratio between the protected volume and the heat loss area.
For OFFICES, major renovation
In the case of renovation works of at least 75% of the building’s heat loss area including the replacement of all technical installations, the requirements to be met are the same as for new tertiary buildings with the application of a 20% flexibility margin (except for overheating risk). This 20% flexibility margin also applies to the requirements of the exemption regime mentioned above.
Brussels Capital Region | |||
| today | from July 2, 2011 | from Dec 31, 2015 | |
| EPB prog | EPB prog | prog ? | |
| E-level | E90 offices and services | E75 offices and services | passive offices and services and very low energy for renovation |
| primary energy | |||
| K-level | K45 offices and services education | ||
Walloon Region | |||||
| today | from Sept 1, 2011 | from 2014 | from 2017 | from 2019 | |
| EPB legal framework | EPB prog | EPB prog | prog ? | prog ? | prog ? |
| E-level | Ew < 100 office and school buildings | Ew < 80 office buildings | low energy | passive | zero energy |
| primary energy | Espec 170 kWh/m².year | Espec 130 kWh/m².year or 468 MJ/m² | |||
| K-level | K45 offices and services K55 industrial buildings | ||||
Flemish Region | ||||
| today | from 2012 | from 2014 | from 2019 | |
| EPB legal framework | EPB prog | EPB prog | EPB prog | prog ? |
| E-level | E100 office buildings | E70* *not yet voted | E60* E70* *not yet voted | nearly zero energy* |
| primary energy | Ep max 70 kWh/m².year | |||
| K-level | K45 offices and services K55 industrial buildings | K40* *not yet voted | ||
- 15 kWh/m².year heating requirement
- 45 kWh/m².year maximum total primary energy
- 0.6 vol/h for air tightness
- 5% maximum acceptable overheating per year
5 criteria for tertiary
- 15 kWh/m².year heating requirement
- 15 kWh/m².year cooling requirement
- 0.6 vol/h for air tightness
- 5% maximum acceptable overheating per year EN 15 251
Need advice for your real estate project?
Allten supports you in your commercial real estate projects while taking into account the standards in force.